DocumentCode
2808334
Title
The negative leader in transformer oil under impulse voltage
Author
Torshin, Yu V.
Author_Institution
Fed. Sci. Centre, All-Russian Electrotech. Inst., Moscow
fYear
2008
fDate
June 30 2008-July 3 2008
Firstpage
1
Lastpage
4
Abstract
The complex experimental studies of the discharge mechanism in transformer oil under negative polarity (NP) of the lightning impulse were carried out using alternative diagnostic methods. Novel data concerning propagation mechanism and parameters of the predischarge channels were obtained. The results indicate that oil breakdown both under negative and positive polarity similar in a number of properties to the breakdown in the long air gaps.
Keywords
lightning; power transformer insulation; transformer oil; diagnostic methods; lightning impulse voltage; negative leader; oil breakdown; predischarge channels; propagation mechanism; transformer oil; Electric breakdown; Electrodes; Electrons; Hydrocarbons; Microchannel; Needles; Oil insulation; Optical propagation; Petroleum; Shock waves;
fLanguage
English
Publisher
ieee
Conference_Titel
Dielectric Liquids, 2008. ICDL 2008. IEEE International Conference on
Conference_Location
Futuroscope-Chasseneuil
Print_ISBN
978-1-4244-1585-4
Electronic_ISBN
978-1-4244-1586-1
Type
conf
DOI
10.1109/ICDL.2008.4622520
Filename
4622520
Link To Document