DocumentCode
2835910
Title
Calculation on electric field intensity of ultra-high voltage transformer coil
Author
Lv, Dianli ; Wang, Youhua ; Zhang, Huijuan ; Zhang, Ping ; Yan, Weili
Author_Institution
Province-Minist. Joint Key Lab. of Electromagn. Field & Electr. Apparatus Reliability, Hebei Univ. of Technol., Tianjin, China
Volume
4
fYear
2010
fDate
22-24 Oct. 2010
Abstract
The 3-D substantial model is built for the bushing end of an ultra-high voltage transformer high-voltage coil and the surrounding of the equipotential shielding. This model is properly simplified according to the symmetrical structure of the coil. The electric field intensity nearby the transformer´s high-intense coil and the surrounding of the equipotential shielding are calculated on the basis of the finite element method. The distribution of the electric field is determined, and the maximum electric field intensity at top and bottom are 8.02×106 V/m and 6.67×106 V/m, respectively. The calculated results can provide basis for coil and equipotential shielding design of an ultra-high voltage transformer.
Keywords
coils; electric fields; finite element analysis; potential transformers; electric field intensity; equipotential shielding; finite element method; ultra high voltage transformer coil; Coils; Electric fields; Oil insulation; Optimization; Power transformer insulation; electric field; finite element method; ultra-high transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
Computer Application and System Modeling (ICCASM), 2010 International Conference on
Conference_Location
Taiyuan
Print_ISBN
978-1-4244-7235-2
Electronic_ISBN
978-1-4244-7237-6
Type
conf
DOI
10.1109/ICCASM.2010.5620515
Filename
5620515
Link To Document