DocumentCode
2851978
Title
The Experimental Research and Analysis of the Reverse Osmosis Technology on the Waste Water Reusing of the Plant Cooling Water
Author
Zhang, Shuguo ; Li, Dong ; Wu, Guohong ; Jiang, Huawei
Author_Institution
Sch. of Environ. Sci. & Eng., North China Electr. Power Univ., Baoding, China
Volume
2
fYear
2009
fDate
16-18 Oct. 2009
Firstpage
843
Lastpage
846
Abstract
This paper studied the influence of the feed water PH value on the reverse osmosis system in the process of the sewage reusing of the power plant circulating water. The utmost recovery rate was made out through experiments, at different feed water PH value, on condition that the concentrated water did not scale. The influence of the PH value on the salt desalting rate of the reverse osmosis system was investigated, the results show that the highest desalination rate is up to 99.6%, when the PH value is 8.0~9.0. Comparing the different operating cost in different operating conditions, it´s found that when the PH value is 8.0, the reverse osmosis systematic recovery rate is 72%, which is the most economical operating condition.
Keywords
cooling; osmosis; sewage treatment; waste recovery; wastewater treatment; plant cooling water; reverse osmosis system; reverse osmosis systematic recovery; reverse osmosis technology; salt desalting rate; sewage reuse; waste water reuse; Biomembranes; Cooling; Costs; Feeds; Paper technology; Power generation; Power generation economics; Reverse osmosis; Water conservation; Water resources; circulating water of power plant; desalting rate; feed water PH value; recovery rate; reverse osmosis;
fLanguage
English
Publisher
ieee
Conference_Titel
Energy and Environment Technology, 2009. ICEET '09. International Conference on
Conference_Location
Guilin, Guangxi
Print_ISBN
978-0-7695-3819-8
Type
conf
DOI
10.1109/ICEET.2009.442
Filename
5365448
Link To Document