DocumentCode :
2880506
Title :
Comparative Reliability of Uninterruptible Power Supply Configurations
Author :
Schwarm, Edward G.
Author_Institution :
Arthur D. Little, Inc.
fYear :
1979
fDate :
26-29 Nov. 1979
Firstpage :
127
Lastpage :
132
Abstract :
This paper compares the reliability of four uninterruptible power supply (UPS) configurations; single module, parallel redundant, static bypass, and static bypass redundant. Equations for calculating the MTBF´s of these configurations are presented along with component reliability estimates. Effects of failure rates of associated circuitry are included. System MTBF´s of 200,000 hours for redundant and 150,000 hours for static bypass systems are now achievable. Guidelines for system type selection are included as performance curves. Effects of aging and appropriate corrective action are discussed.
Keywords :
Batteries; Current supplies; Equations; Inverters; Maintenance; Power industry; Power supplies; Power system reliability; Rectifiers; Uninterruptible power systems;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, 1979. INTELEC 1979. International
Conference_Location :
Washington, DC, USA
Type :
conf
DOI :
10.1109/INTLEC.1979.4793614
Filename :
4793614
Link To Document :