Abstract
This paper outlines a method for determining required battery and rectifier capacities in central offices. Constant and nearly constant office loads are considered, representative of digital switching and transmission systems. The battery capacity is computed from the full-load current, the required reserve time, the depth of discharge, the end-of-life capacity, and an allowance for converter loads. The rectifier capacity is then determined to supply the load current and recharge the selected battery in a specified time. It is shown how the rectifier capacity may be selected to ensure a recharge time of 40 hours from full discharge, in the presence of one failed rectifier.
Keywords
Batteries; Central office; Chromium; Communication system traffic control; Control systems; Current supplies; Digital control; Rectifiers; Switching systems; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1982. INTELEC 1982. International
Conference_Location
Washington, DC, USA