DocumentCode :
2906120
Title :
Optimal placement of power quality monitors in distribution systems using the topological monitor reach area
Author :
Ibrahim, Ahmad Asrul ; Mohamed, Azah ; Shareef, Hussain
Author_Institution :
Dept. of Electr., Electron. & Syst. Eng., Univ. Kebangsaan Malaysia, Bangi, Malaysia
fYear :
2011
fDate :
15-18 May 2011
Firstpage :
394
Lastpage :
399
Abstract :
Installation of power quality monitors (PQMs) at all buses in a power distribution network is uneconomical and it needs to be minimized. This paper presents a PQM positioning technique which finds the optimal number and location of PQMs in power distribution systems for voltage sag detection. The IEEE 34-node and 69 bus test systems were modeled in DIgSILENT software to obtain the topological monitor reach area matrix for various types of faults. Then, an optimization problem is formulated and solved using genetic algorithm to find the minimum number of PQMs in the distribution system which can guarantee the observability of the whole system. Finally, the sag severity index has been used to find the best location to install monitors in the distribution system.
Keywords :
distribution networks; power supply quality; IEEE 34-node; PQM positioning technique; bus test system; genetic algorithm; optimal placement; optimization; power distribution network; power quality monitoring; voltage sag detection; Genetic algorithms; Monitoring; Optimization; Power quality; Voltage fluctuations; Voltage measurement; distribution system; power quality monitor (PQM); sag severity index (SSI); topological monitor reach area (TMRA); voltage sag detection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Machines & Drives Conference (IEMDC), 2011 IEEE International
Conference_Location :
Niagara Falls, ON
Print_ISBN :
978-1-4577-0060-6
Type :
conf
DOI :
10.1109/IEMDC.2011.5994627
Filename :
5994627
Link To Document :