• DocumentCode
    2912414
  • Title

    Vacuum circuit breaker´s electrical life for shunt capacitor switching

  • Author

    Griot, S. ; Moreau, A.

  • Author_Institution
    Schneider Electr., ZAC champ St. ange, Varces, France
  • fYear
    2010
  • fDate
    Aug. 30 2010-Sept. 3 2010
  • Firstpage
    194
  • Lastpage
    197
  • Abstract
    In order to improve the efficiency of power distribution and for economic reasons, the power factor is corrected on medium voltage electrical network. To do this, it is mandatory to switch once or twice a day a capacitor bank. Vacuum circuit breakers are frequently used to switch capacitor banks. An automated system is used to evaluate the electrical life of vacuum circuit breakers depending on the shunt capacitor switching parameters. Tests consist of opening and closing operations on a three-phase circuit breaker. This system has two main advantages; the maximum reactive power available is 20 Mvar at 24 kV with inrush currents up to 22 kA (common values in customer applications are under 10 kA) and the short endurance test duration is only 8 days for 10,000 operations compared to 5 weeks in laboratories.
  • Keywords
    capacitor switching; power distribution economics; power factor; vacuum circuit breakers; automated system; current 22 kA; electrical life; power distribution; power factor; shunt capacitor switching; three-phase circuit breaker; time 5 week; time 8 d; vacuum circuit breaker; voltage 24 kV; Capacitors; Circuit breakers; Couplings; Interrupters; Surges; Switches; Switching circuits;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum (ISDEIV), 2010 24th International Symposium on
  • Conference_Location
    Braunschweig
  • ISSN
    1093-2941
  • Print_ISBN
    978-1-4244-8367-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2010.5625750
  • Filename
    5625750