Vacuum circuit breaker´s electrical life for shunt capacitor switching
Author
Griot, S. ; Moreau, A.
Author_Institution
Schneider Electr., ZAC champ St. ange, Varces, France
fYear
2010
fDate
Aug. 30 2010-Sept. 3 2010
Firstpage
194
Lastpage
197
Abstract
In order to improve the efficiency of power distribution and for economic reasons, the power factor is corrected on medium voltage electrical network. To do this, it is mandatory to switch once or twice a day a capacitor bank. Vacuum circuit breakers are frequently used to switch capacitor banks. An automated system is used to evaluate the electrical life of vacuum circuit breakers depending on the shunt capacitor switching parameters. Tests consist of opening and closing operations on a three-phase circuit breaker. This system has two main advantages; the maximum reactive power available is 20 Mvar at 24 kV with inrush currents up to 22 kA (common values in customer applications are under 10 kA) and the short endurance test duration is only 8 days for 10,000 operations compared to 5 weeks in laboratories.
Keywords
capacitor switching; power distribution economics; power factor; vacuum circuit breakers; automated system; current 22 kA; electrical life; power distribution; power factor; shunt capacitor switching; three-phase circuit breaker; time 5 week; time 8 d; vacuum circuit breaker; voltage 24 kV; Capacitors; Circuit breakers; Couplings; Interrupters; Surges; Switches; Switching circuits;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum (ISDEIV), 2010 24th International Symposium on
Conference_Location
Braunschweig
ISSN
1093-2941
Print_ISBN
978-1-4244-8367-9
Electronic_ISBN
1093-2941
Type
conf
DOI
10.1109/DEIV.2010.5625750
Filename
5625750
Link To Document