DocumentCode
2932089
Title
Analysis and Discussion of SF6 Byproducts in Simulated Electric Equipment of Overheating Faults in Low Humidity
Author
Wang, Yu ; Li, Li ; Yao, Weijian
Author_Institution
Environ. Protection Dept., Electr. Power Test Res. Inst., Guangzhou, China
fYear
2011
fDate
25-28 March 2011
Firstpage
1
Lastpage
3
Abstract
The decomposition of sulfur hexafluoride (SF6) in overheated electric equipment at different temperature in low humidity was simulated in the study. SF6 is very stable and not significantly decomposed at 200°C, 250°C and 300°C. SF6 is significantly decomposed at 350°C. SF6 is more easily to be decomposed and decomposed more rapidly at higher temperature.
Keywords
SF6 insulation; electrical faults; SF6 byproduct; low humidity; overheating fault simulated electric equipment; sulfur hexafluoride decomposition; temperature 200 degC; temperature 250 degC; temperature 300 degC; temperature 350 degC; Hafnium; Heating; Humidity; Impurities; Moisture; Power systems; Sulfur hexafluoride;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location
Wuhan
ISSN
2157-4839
Print_ISBN
978-1-4244-6253-7
Type
conf
DOI
10.1109/APPEEC.2011.5748656
Filename
5748656
Link To Document