• DocumentCode
    2941465
  • Title

    Analysis of the Energization Test of a Half-Wavelength AC Link Composed of Similar Transmission Lines

  • Author

    Gomes, Elson Costa ; Tavares, Maria Cristina

  • Author_Institution
    Sch. of Electr. & Comput. Eng., Univ. of Campinas, Campinas, Brazil
  • fYear
    2011
  • fDate
    25-28 March 2011
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper presents the analysis of the use of similar transmission lines to represent a trunk of a little more than a half wavelength (HWL+) in order to conduct an on-site energization test. Some results of the possible reflections that may occur at the interconnection of similar lines are analyzed and also it is established boundary conditions of different transmission lines that can still represent a HWL+ trunk in order to enable similar tests within different power grid. The validation of the AC-Link Test formed by different transmission lines is performed through the analysis of two-port elements constants in the frequency range of interest. Time domain simulations are also presented to the studied trunk.
  • Keywords
    power system interconnection; power transmission lines; two-port networks; AC-link test; HWL+ trunk; electromagnetic transient; half-wavelength AC link; on-site energization test; power system interconnection; similar transmission lines; two-port elements; Capacitance; Frequency domain analysis; Frequency response; Impedance; Power transmission lines; Substations; Surges;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
  • Conference_Location
    Wuhan
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4244-6253-7
  • Type

    conf

  • DOI
    10.1109/APPEEC.2011.5749121
  • Filename
    5749121