• DocumentCode
    2969306
  • Title

    Analysis of current transfer process during the open operating in large current vacuum interrupters with dual-contact

  • Author

    Li Yu ; Shun Yuan ; Feng Li

  • Author_Institution
    Dept. of Electr. Eng., Shenyang Inst. of Eng., Shenyang, China
  • fYear
    2012
  • fDate
    2-7 Sept. 2012
  • Firstpage
    197
  • Lastpage
    200
  • Abstract
    A new type of “dual-contact” structure of vacuum interrupter is proposed in the paper. It consists of main contact and arc contact, which are used to carry rated current and break short circuit current, respectively. During the closing/opening of vacuum circuit breaker, arc contact is first closed and post breaking, however, main contact is post closed and first breaking. So there must be the current transfer process. In this paper, during the breaking process of vacuum circuit breaker, a model of current transfer is used in the investigation of current transfer, and the maximum possible current transfer time is obtained. This analysis is helpful to the research of large current vacuum interrupters with dual-contact.
  • Keywords
    arcs (electric); electrical contacts; short-circuit currents; vacuum interrupters; arc contact; breaking process; current transfer process analysis; dual-contact structure; large current vacuum interrupters; short circuit current; Circuit breakers; Integrated circuit modeling; Interrupters; Resistance; SPICE; Short circuit currents; Springs;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum (ISDEIV), 2012 25th International Symposium on
  • Conference_Location
    Tomsk
  • ISSN
    1093-2941
  • Print_ISBN
    978-1-4673-1263-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2012.6412486
  • Filename
    6412486