Abstract
The vacuum vessel of RFX has been designed to operate between room temperature and 350°C during the experimental sessions and during first wall conditioning operations. The temperature control system of the vacuum vessel consists of the measurement and the heating system, connected to the RFX central control system, SIGMA. The data acquisition electronics supplies the temperature signals to the heating system and to SIGMA. The heating system provides uniform heating in both toroidal and poloidal directions. SIGMA allows different modes of operation and handles the alarm signal. After a description of the main components, the results of the first two years of operation are presented
Keywords
alarm systems; data acquisition; fusion reactor design; fusion reactor operation; fusion reactor safety; fusion reactors; power system control; reversed field pinch; temperature control; vacuum apparatus; vacuum control; vacuum measurement; RFX; SIGMA; alarm signal; central control system; data acquisition electronics; first wall conditioning operations; fusion reactor; heating system; poloidal direction; reversed field pinch; room temperature; temperature control system; toroidal direction; uniform heating; vacuum vessel temperature control; Cables; Centralized control; Control systems; Cooling; Heating; Plasma temperature; Temperature control; Temperature measurement; Temperature sensors; Vacuum systems;
fLanguage
English
Publisher
ieee
Conference_Titel
Fusion Engineering, 1993., 15th IEEE/NPSS Symposium on
Conference_Location
Hyannis, MA
Print_ISBN
0-7803-1412-3
Type
conf
DOI
10.1109/FUSION.1993.518386
Filename
518386
Link To Document