Title :
Investigating suitable positions in power transformers for installing UHF antennas for partial discharge localization
Author :
Mirzaei, H. ; Akbari, A. ; Zanjani, M. ; Miralikhani, K. ; Gockenbach, E. ; Borsi, H.
Author_Institution :
Dept. of Electr. Eng., K.N. Toosi Univ. of Technol., Tehran, Iran
Abstract :
One of the critical points in the UHF partial discharge (PD) localization in power transformers is the installation position of the UHF antennas inside the transformer or on its tank. In the UHF localization method which is based on comparing the differences of the arrival times of the partial discharge electromagnetic waves, ideally at least four antennas must be used to have an effective localization. Mechanical limitations such as the existence of iron tank and high electric field intensity inside transformer must be considered in installing UHF antenna. Beside these problems, the effect of antennas positions on localization accuracy must be taken into account. The positions of the antennas have a direct relation with arrival time differences for potential PD positions inside transformer. In this paper a method to identify best places for antennas installation is proposed to obtain more accurate defect localization.
Keywords :
UHF antennas; electric field effects; electromagnetic waves; partial discharges; power transformers; UHF antennas; UHF localization; electric field intensity; four antennas; installation position; iron tank; mechanical limitations; partial discharge electromagnetic waves; partial discharge localization; power transformers; Correlation; Oil insulation; Partial discharges; Power transformers; UHF antennas; UHF localization; partial discharge; power transformer;
Conference_Titel :
Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
Conference_Location :
Bali
Print_ISBN :
978-1-4673-1019-2
DOI :
10.1109/CMD.2012.6416223