Abstract :
The proliferation of nonlinear loads causes harmonic voltage distortion on public and industrial networks. The transformer´s thermal loss of life, estimated for sinusoidal loads, can be slightly reduced if we consider the harmonic currents. In this paper we study a distribution transformer (630 kVA) loss of life, driving a load cycle including a sinusoidal load and a weighted distorting one. The transformer thermal and electrical models are presented and the simulation results are analyzed. We propose a general expression to characterize loss of life derating; this expression includes only the current total harmonic distortion and two transformer specific parameters
Keywords :
harmonic distortion; industrial power systems; load (electric); maintenance engineering; power electronics; power transformers; 630 kVA; current total harmonic distortion; distorting power electronic loads; electrical model; harmonic currents; harmonic voltage distortion; industrial networks; load cycle; loss of life derating characterisation; nonlinear loads; power transformers life expectancy; public networks; sinusoidal loads; thermal loss of life; thermal model; weighted distorting load; Aging; Copper; Magnetic cores; Oil insulation; Petroleum; Power transformers; Temperature; Thermal conductivity; Thermal loading; Transformer cores;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial Electronics, 1996. ISIE '96., Proceedings of the IEEE International Symposium on
Conference_Location :
Warsaw
Print_ISBN :
0-7803-3334-9
Type :
conf
DOI :
10.1109/ISIE.1996.551007
Filename :
551007
Link To Document :
بازگشت