    Computer aided recognition of defects in GIS

  • Author

    Ziomek, W. ; Schlemper, H.-D. ; Feser, K.

  • Author_Institution
    Inst. of Electr. Power Eng., Poznan Univ. of Technol., Poland
  • Volume
    1
  • fYear
    1996
  • fDate
    16-19 Jun 1996
  • Firstpage
    91
  • Abstract
    A computerized pattern recognition system based on phase resolved partial discharge (PRPD) measurements has been developed. The paper presents results of defect classification obtained for various GIS installations. The system is trained to distinguish between seven basic defect types, such as voids in spacers, moving metallic particles, protrusions on electrodes and floating electrodes. The defect classification is based on 60 parameters extracted from PRPD patterns and utilizes different recognition algorithms. Tests with a database of more than 600 individual measurements gave satisfactory results. Tests with multiple defects and disturbed measurements were done. The database was collected during laboratory experiments and on-site tests of GIS installations
  • Keywords
    electrodes; gas insulated substations; pattern recognition; power engineering computing; voids (solid); GIS; computerized pattern recognition system; defect classification; disturbed measurements; electrode protrusions; floating electrodes; moving metallic particles; multiple defects; on-site tests; phase resolved partial discharge; recognition algorithms; spacers; voids; Classification algorithms; Databases; Geographic Information Systems; Partial discharges; Pattern analysis; Pattern recognition; Power engineering computing; Pulse measurements; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
  • Conference_Location
    Montreal, Que.
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-3531-7
  • Type

    conf

  • DOI
    10.1109/ELINSL.1996.549290
  • Filename
    549290