DocumentCode :
304278
Title :
Effects of geometric configuration on the cooling performance of a Vuilleumier cycle heat pump
Author :
Lee, Geon Tae ; Kang, Byung Ha ; Yoo, Hoseon
Author_Institution :
Air Condtioning & Environ. Control Lab., Korea Inst. of Sci. & Technol., Seoul, South Korea
Volume :
2
fYear :
1996
fDate :
11-16 Aug 1996
Firstpage :
781
Abstract :
An experimental study has been carried out investigate the effects of the combination of different wire mesh numbers (in the regenerator), and the tube number (in the cooler) on the cooling performance of a Vuilleumier cycle heat pump. A wide range of charging pressures, heater tube temperatures and revolution speeds are also considered. The results indicate that the cooling performance is improved with the proper combination of different wire meshes in the cold regenerator. More tubes in a cooler are desirable for better cooling performance. It is also found that the cooling capacity is enhanced, whereas coefficient of performance (COP) is reduced, with an increase in the heater tube temperature and revolution speed. Both the cooling capacity and COP are increased with a higher charging pressure
Keywords :
cooling; geometry; heat pumps; thermal analysis; Vuilleumier cycle heat pump; charging pressures; coefficient of performance; cold regenerator; cooler; cooling capacity; cooling performance; geometric configuration; heater tube temperatures; revolution speeds; tube number; wire mesh number; Air conditioning; Cooling; Geometry; Heat pumps; Mechanical engineering; System performance; Temperature control; Temperature distribution; Thermal pollution; Wire;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Conversion Engineering Conference, 1996. IECEC 96., Proceedings of the 31st Intersociety
Conference_Location :
Washington, DC
ISSN :
1089-3547
Print_ISBN :
0-7803-3547-3
Type :
conf
DOI :
10.1109/IECEC.1996.553796
Filename :
553796
Link To Document :
بازگشت