Title :
Breakdown characteristics of rod-plane gap under salt fog for AC and DC voltages
Author :
Vasudev, N. ; Ravi, K.N. ; Mujumdar, A.K. ; Ratra, M.C.
Author_Institution :
Central Power Res. Inst., Bangalore, India
Abstract :
AC and DC breakdown test results are presented for rod-plane gaps under salt fog. It is found that, in general, there may be no significant change in the breakdown values of the gaps even under severe saline pollution in case of both AC and DC voltages. The breakdown voltage values are, however, very much lower in the case of DC negative voltages under salt fog conditions than under dry conditions. This may be one of the reasons for the arc bridging of the underribs of a polluted insulator under DC negative voltages
Keywords :
air pollution; arcs (electric); electric breakdown of gases; insulators; spark gaps; AC voltages; DC voltages; arc bridging; breakdown test results; negative voltages; polluted insulator; rod-plane gap; saline pollution; salt fog; underribs; Breakdown voltage; Collision mitigation; Electric breakdown; Flashover; Insulation; Laboratories; Physics; Pollution; Power systems; Testing;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1990. Annual Report., Conference on
Conference_Location :
Pocono Manor, PA
DOI :
10.1109/CEIDP.1990.201400