Title :
Measured impedance at relaying point for inter phase faults on next line
Author :
Shateri, H. ; Jamali, S.
Author_Institution :
Center of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol.
Abstract :
Distance relays are one of the mostly used protective devices in the transmission systems. These relays are used as the main, First zone and a part of second zone, and the backup, the rest of second zone and third zone, protective devices. Fault resistance is a source of error for distance relays in the form of the measured impedance deviation from its actual value. This paper investigates the measured impedance by distance relays for the faults on the protected and next line in the case of inter phase, phase to phase and three phase, faults by means of presenting measured impedance and investigating its variation duo the changes in the power system conditions.
Keywords :
power transmission faults; power transmission protection; relay protection; distance relays; fault resistance; interphase faults; power system conditions; protective devices; transmission systems; Electrical resistance measurement; Impedance measurement; Phase measurement; Power measurement; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying; Relays;
Conference_Titel :
Universities Power Engineering Conference, 2008. UPEC 2008. 43rd International
Conference_Location :
Padova
Print_ISBN :
978-1-4244-3294-3
Electronic_ISBN :
978-88-89884-09-6
DOI :
10.1109/UPEC.2008.4651508