DocumentCode :
3109253
Title :
Transformer condition assessment with the Tettex recovery voltage method
Author :
Webb, Michael
fYear :
1996
fDate :
35404
Firstpage :
42370
Lastpage :
42374
Abstract :
All oil-paper transformers contain some water in their solid insulation. The Tettex Recovery Voltage Meter (RVM) is a method for determining the moisture content in the paper so that the effects on dielectric integrity, loading capability and residual life expectancy can be estimated. The author discusses the problems of moisture in paper insulation, the polarisation effects and polarisation spectrum measurement using the Tettex RVM. Practical applications of the method are outlined and it is compared with other methods
fLanguage :
English
Publisher :
iet
Conference_Titel :
Monitors and Condition Assessment Equipment (Digest No. 1996/186), IEE Colloquium on
Conference_Location :
Leatherhead
Type :
conf
DOI :
10.1049/ic:19961064
Filename :
600661
Link To Document :
بازگشت