Title :
A voltage sag study in a large industrial distribution system
Author :
Bollen, M.H.J. ; Yalçinkaya, G. ; Pellis, J. ; Qader, M.R.
Author_Institution :
Centre for Electr. Energy, Univ. of Manchester Inst. of Sci. & Technol., UK
Abstract :
The method of fault positions has been used to study the post-fault voltage sags in the supply to a large chemical industry plant. The main concern is faults in the on-site distribution systems. The during-fault and post-fault voltages have been simulated by using the PSCAD/EMTDC package. A comparison with a measured sag has been made, showing good agreement. The simulation results taught us that post-fault voltage sags mainly occur during faults in the MV networks. Strengthening the supply, or reducing the (post-fault) motor load are needed to solve this
Keywords :
chemical industry; distribution networks; fault location; industrial plants; industrial power systems; power system analysis computing; MV networks; PSCAD/EMTDC package; chemical industry plant; during-fault voltages; industrial distribution system; measured voltage sag; motor load reduction; post-fault voltage sags; supply strengthening; voltage sag; voltage simulation; Chemical industry; Chemical technology; Costs; Induction motors; Low voltage; Power quality; Power system stability; Redundancy; Shape; Voltage fluctuations;
Conference_Titel :
Industry Applications Conference, 1996. Thirty-First IAS Annual Meeting, IAS '96., Conference Record of the 1996 IEEE
Conference_Location :
San Diego, CA
Print_ISBN :
0-7803-3544-9
DOI :
10.1109/IAS.1996.563903