Improvement of power system transient stability by superconducting fault current limiter
Author :
Yagami, Masaki ; Shibata, Shinsuke ; Murata, Toshiaki ; Tamura, Junji
Abstract :
This paper presents the results of analyses of the effectiveness of a superconducting fault current limiter (SFCL) on improving power system transient stability and limiting the fault current in a two-machine-infinite bus system. In this study, the system model with two SFCLs installed at each generator terminal was used taking 3LG (three lines to ground) fault at 12 fault points into account. These analyses were performed using EMTP/ATP. It is concluded that the use of SFCL with shunt resistance value of about 1.0 pu is effective for all fault points for the improvement of power system transient stability and the limiting of fault current.
Keywords :
EMTP; fault current limiters; power system transient stability; superconducting devices; EMTP/ATP; fault current limiting; fault points; generator terminal; power system transient stability improvement; shunt resistance value; superconducting fault current limiter; three lines to ground fault; two-machine-infinite bus system; Circuit faults; Electric resistance; Fault current limiters; Fault currents; Power system modeling; Power system reliability; Power system simulation; Power system stability; Power system transients; Superconducting transmission lines;