• DocumentCode
    3168779
  • Title

    Study of very fast transient overvoltages and mitigation techniques of a gas insulated substation

  • Author

    Pathak, Nikhil ; Bhatti, T.S. ; Ibraheem

  • Author_Institution
    Jamia Millia Islamia Univ., New Delhi, India
  • fYear
    2015
  • fDate
    19-20 March 2015
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The very fast transient overvoltages (VFTOs) generated due to switching operations of gas insulated substations (GIS) are dangerous to the equipments connected to the substations. In special cases these transients may cross the Basic Insulation Level (BIL) of the GIS. In this paper, these transient voltages are investigated at the different sensitive locations of a 400 KV GIS. VFTOs of the GIS are calculated using EMTDC/PSCAD software. Hence, the suppression of the VFTOs is also an important field of interest. The suppression techniques to reduce the VFTOs are also discussed in this paper.
  • Keywords
    EMTP; gas insulated substations; overvoltage protection; power system transients; BIL; EMTDC; GIS; PSCAD software; VFTO suppression; basic insulation level; gas insulated substations; mitigation technique; switching operation; very fast transient overvoltage; Gas insulation; Power transformers; Substations; Surges; Switches; Transient analysis; Air insulated substations (AIS); Basic insulation level (BIL); Gas insulated substation (GIS); Very fast transient overvoltages (VFTOs);
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Circuit, Power and Computing Technologies (ICCPCT), 2015 International Conference on
  • Conference_Location
    Nagercoil
  • Type

    conf

  • DOI
    10.1109/ICCPCT.2015.7159278
  • Filename
    7159278