DocumentCode :
3185593
Title :
Adaptive reclosure using high frequency fault transients
Author :
Li Youyi ; Xinzhou, Li Youyi Dong ; Bo, Z.Q. ; Chin, N.F. ; Ge Yaozhang
Author_Institution :
Xi´´an Jiaotong Univ., China
fYear :
2001
fDate :
2001
Firstpage :
375
Lastpage :
378
Abstract :
A new signal processing algorithm for arcing faults detection based on the high frequency current transient is presented in this paper. In transient faults, arc current extinguishes and then ignites, and this periodically disturbs fault current. After several cycles, when transient signals by the fault decay a lot, the arc disturbance can be identified by the wavelet transform. The feasibility of this algorithm has been tested by computer simulation
Keywords :
arcs (electric); power system faults; power system transients; signal processing; wavelet transforms; adaptive reclosure; arc current; arc disturbance identification; arcing faults detection; computer simulation; fault current; high frequency current transient; high frequency fault transients; signal processing algorithm; transient faults; wavelet transform;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
Conference_Location :
Amsterdam
ISSN :
0537-9989
Print_ISBN :
0-85296-732-2
Type :
conf
DOI :
10.1049/cp:20010178
Filename :
929341