Title :
A fault location algorithm for transmission line based on distributed parameter
Author :
Chen, Zheng ; Luo, Chengmu ; Su, Jinxi ; Wu, Xinrong
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
A fault location algorithm based on distributed parameter using synchronized samples with the Global Positioning System (GPS) is described. The fault location algorithm is based on a distributed parameter, it can eliminate the effect of line shunt capacitance automatically. Considering untransposed and unbalanced transmission lines practically, phase components are transformed to model components in the fault location algorithm. Computer simulation and experiment showed that the algorithm not only has high accuracy and robustness, but also is not affected by fault resistance, fault type, fault location and incidence angle of the fault occurrence. The location error is less than 0.4% for all cases
Keywords :
Global Positioning System; capacitance; fault location; power transmission faults; power transmission lines; synchronisation; Global Positioning System; computer simulation; distributed parameter; fault location; fault location algorithm; fault occurrence; fault resistance; fault type; incidence angle; line shunt capacitance; location error; phase components; robustness; synchronized samples; transmission line; unbalanced transmission lines; untransposed transmission lines;
Conference_Titel :
Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
Conference_Location :
Amsterdam
Print_ISBN :
0-85296-732-2
DOI :
10.1049/cp:20010187