DocumentCode :
3192373
Title :
Power Systems Fault Type Identification Based on Park´s Transformation Algorithm
Author :
Soliman, S.A. ; Belkhayat, M.
Author_Institution :
Dept. of Electr. Eng., Qatar Univ.
fYear :
2006
fDate :
26-28 July 2006
Firstpage :
141
Lastpage :
145
Abstract :
Fault identification is necessary for system protection and the selection of suitable relays, which are required for the subsequent fault isolation. In this paper, fault identification is achieved using a simple and numerically efficient algorithm based on Park´s transformations. The algorithm uses two transformation matrices. The first matrix is used to filter out the dc offset and harmonics that contaminate the three-phase voltage signal. The second transformation is used to estimate the positive and negative sequence components. The zero sequence components are estimated from the first transformation matrix. Results based on detailed system models are presented in the paper. Having identified the positive sequence, negative sequence and zero sequence components, the fault type can easily be identified
Keywords :
fault diagnosis; matrix algebra; power harmonic filters; power system faults; power system protection; Park transformations; fault isolation; negative sequence components; positive sequence components; power systems fault type identification; transformation matrices; zero sequence components; Equations; Fault diagnosis; Frequency; Power harmonic filters; Power system faults; Power system protection; Power system relaying; Sampling methods; Transmission line matrix methods; Voltage; Positive; control; negative; zero sequence;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering, 2006 Large Engineering Systems Conference on
Conference_Location :
Halifax, NS
Print_ISBN :
1-4244-0556-4
Electronic_ISBN :
1-4244-0557-2
Type :
conf
DOI :
10.1109/LESCPE.2006.280377
Filename :
4059383
Link To Document :
بازگشت