Title :
System protection and control task force´s initial recommendations concerning NERC recommendation 8A loadability requirements on transmission protective relaying systems
Abstract :
This paper discusses with system protection and control task force´s initial recommendations concerning with NERC recommendation 8A loadability requirements on transmission protective relaying systems. The NERC investigation team recommends that the zone 3 relay, if used, should not operate at or below 150% of the emergency ampere rating of a line, assuming a .85 per unit voltage and a line phase angle of 30 degrees. The planning committee shall review such exceptions to ensure they do not increase the risk of widening a cascading failure of the power system.
Keywords :
power system relaying; power transmission lines; power transmission planning; power transmission protection; relay protection; risk analysis; 8A loadability; NERC recommendation; cascading failure; control task; emergency ampere rating; line phase angle; planning committee shall; power system risk; transmission protective relaying systems; Call conference; Certification; Control systems; Electrical equipment industry; Force control; Power system planning; Power system relaying; Protection; Protective relaying; Relays;
Conference_Titel :
Protective Relay Engineers, 2005 58th Annual Conference for
Print_ISBN :
0-7803-8896-8
DOI :
10.1109/CPRE.2005.1430438