DocumentCode :
3238859
Title :
Use of portable protective gaps on the California-Oregon transmission project compact 550 kV line
Author :
Gela, G. ; Kientz, H. ; Gillies, D.A. ; Mitchell, J.D. ; Lyons, P.F.
Author_Institution :
EPRI Power Delivery Centre, Lenox, MA, USA
fYear :
1995
fDate :
29 Oct-3 Nov 1995
Firstpage :
156
Lastpage :
162
Abstract :
This paper presents result of research on the application of a portable protective gap (PPG) to live work on a compact 550 kV steel lattice tower, The objective of the research was to provide experimental evidence which confirms the needed coordination of the PPG sparkover characteristics with the sparkover characteristics of the worksite on the compact tower during live work. Sparkover characteristics of the worksite are strongly affected by the presence of the worker, the live working tools, and damaged insulators
Keywords :
flashover; health hazards; insulators; maintenance engineering; poles and towers; safety; steel; 550 kV; California-Oregon transmission project; compact steel lattice tower; damaged insulators; live work; live working tools; portable protective gap; sparkover characteristics; worksite; Conductors; Control systems; Electrical safety; Occupational safety; Occupational stress; Poles and towers; Power system transients; Power transmission lines; Protection; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Construction and Live Line Maintenance, 1995. ESMO-95 Proceedings., Seventh International Conference on
Conference_Location :
Columbus, OH
Print_ISBN :
0-7803-2506-0
Type :
conf
DOI :
10.1109/TDCLLM.1995.485051
Filename :
485051
Link To Document :
بازگشت