Abstract :
A step by step method for determining controlled and conventional series compensation requirements is developed. The Montana 500 kV transmission system is taken as an example in this study. A base transfer rating of 2200 MW for the system already exists, and it is assumed that as its power loading increases, controlled series compensation is needed to reinforce the system. Combination of conventional and thyristor-controlled series compensators (TCSCs) is considered as a means of increasing the system transfer capability. Power flow and transient stability studies are performed to rate and size the series compensators. The TCSC reactance control capabilities are established for steady-state and transient conditions. An installation sequence is developed relating facility requirements to system loading
Keywords :
compensation; load flow; power capacitors; power system stability; power system transients; power transmission lines; thyristor applications; 2200 MW; 500 kV; FACTS; Montana transmission system; base transfer rating; controlled series compensation; power flow; power loading; reactance control capabilities; series compensation rating; series compensation sizing; steady-state conditions; system transfer capability; thyristor-controlled series compensators; transient stability; transmission system planning; DC generators; Inductors; Load flow; Power capacitors; Power generation; Power system planning; Power transmission lines; Samarium; Stability; Thyristors;
Conference_Titel :
Northcon 95. I EEE Technical Applications Conference and Workshops Northcon95
Conference_Location :
Portland, OR
Print_ISBN :
0-7803-2639-3
DOI :
10.1109/NORTHC.1995.485084