DocumentCode
3248667
Title
Review of 20 kV Overhead Distribution Lines Reliability Against Lightning at PLN APJ Bogor
Author
Zoro, R. ; Mefiardhi, R. ; Rosidin, A. ; Poerwanto, E.
Author_Institution
Sch. of Electr. Eng. & Informatics, Inst. of Technol., Bandung
fYear
2006
fDate
38869
Firstpage
455
Lastpage
459
Abstract
Because the low insulation strength of distribution lines, virtually all strokes that terminate on the phase conductors of a distribution lines will result in flashover. However, in some cases, shield wire may provide some measure of protection from these direct strokes. Distribution lines are also subjected to over voltages induced by strokes that terminate adjacent to the line. In fact, most of the flashovers that occur are cause by these induced voltages. This paper gives a review on existing condition on unimproved distribution lines in Bogor and some improvement that has to be made. Bogor is well known as a highest lightning activity area in Indonesia, with over 300 thunderstorm days a year
Keywords
flashover; overvoltage protection; power distribution protection; power distribution reliability; power overhead lines; thunderstorms; 20 kV; Indonesia; PLN APJ Bogor; flashover; lightning; low insulation strength; over voltage; overhead distribution lines reliability; phase conductor; thunderstorm; Breakdown voltage; Conductors; Dielectrics and electrical insulation; Flashover; Lightning; Power distribution lines; Protection; Solids; Voltage control; Wire; critical flashover voltage (CFO); flashover rate; line insulator; outages cause by lightning;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and applications of Dielectric Materials, 2006. 8th International Conference on
Conference_Location
Bali
Print_ISBN
1-4244-0189-5
Electronic_ISBN
1-4244-0190-9
Type
conf
DOI
10.1109/ICPADM.2006.284213
Filename
4062702