DocumentCode
3255508
Title
Dissolved gas analysis of alternative dielectric fluids under thermal and electrical stress
Author
Jovalekic, M. ; Vukovic, D. ; Tenbohlen, S.
Author_Institution
Inst. of Power Transm. & High Voltage Technol. (IEH), Univ. of Stuttgart, Stuttgart, Germany
fYear
2011
fDate
26-30 June 2011
Firstpage
1
Lastpage
4
Abstract
Dissolved gas in oil analysis (DGA) has been used for many years successfully for diagnosis and condition monitoring of mineral oil filled transformers. In future the diagnostic methods have to be transferred to new fluids. This contribution presents results of the gassing behavior of different insulating liquids from experiments, which represent electrical and thermal faults. Also the suitability of existing mineral oil interpretation methods for DGA is considered. The main investigated fluid is Envirotemp® FR3™. Where possible the amount and relation of the gases are compared to mineral oil and other synthetic esters gassing behaviour.
Keywords
chemical analysis; condition monitoring; dissolving; fault diagnosis; minerals; power transformer insulation; thermal stresses; transformer oil; DGA; condition monitoring; diagnostic methods; dielectric fluids; dissolved gas analysis; electrical stress; insulating liquids; mineral oil; oil analysis; synthetic esters; thermal stress; transformers oil; Discharges; Gases; Generators; Minerals; Power transformers; Transformer oil; dissolved gas analysis; natural ester;
fLanguage
English
Publisher
ieee
Conference_Titel
Dielectric Liquids (ICDL), 2011 IEEE International Conference on
Conference_Location
Trondheim
ISSN
2153-3725
Print_ISBN
978-1-4244-7352-6
Electronic_ISBN
2153-3725
Type
conf
DOI
10.1109/ICDL.2011.6015457
Filename
6015457
Link To Document