DocumentCode :
3278690
Title :
A New Method of On-line Medium Frequency Partial Discharge Monitoring for Power Transformer Based on Double Sensors Directionally Coupling Signal
Author :
Liao, Yancqun ; Xu, Yang ; Qiu, Changrong ; Xi, Baofeng ; Liu, Xinying ; Feng, Yi ; Fang, Qiong
fYear :
2007
fDate :
8-13 July 2007
Firstpage :
596
Lastpage :
599
Abstract :
This paper introduces an on-line monitoring method for power transformers, using double magnetic core current sensors directionally coupling signal to limit interference using a polarity discrimination method. The transient models of transformer windings are set up, and considering the characteristic of the current sensors and transformer windings, the testing frequency band is chosen from 1MHz to3MHz. The reliability of polarity discrimination method to limit interference is verified over this frequency range.
Keywords :
Couplings; Frequency; Interference; Magnetic cores; Magnetic sensors; Monitoring; Partial discharges; Power transformers; Sensor phenomena and characterization; Windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
Conference_Location :
Winchester, UK
Print_ISBN :
1-4244-0750-8
Electronic_ISBN :
1-4244-0751-6
Type :
conf
DOI :
10.1109/ICSD.2007.4290884
Filename :
4290884
Link To Document :