DocumentCode
3278922
Title
Diagnostic of Pre-breakdown State of Polymeric Insulators by the Thermovision Method
Author
Gefle, O.S. ; Lebedev, S.M.
Author_Institution
High Voltage Research Institute of Tomsk Polytechnic University, 2A, Lenin Avenue, 634050, Tomsk, Russia. E-mail: polymer@hvd.tsk.ru
fYear
2007
fDate
8-13 July 2007
Firstpage
647
Lastpage
650
Abstract
The possibility of diagnosing the pre-breakdown state of polymeric insulators by the thermovision method is represented in this paper. The diagnostic method is based on the monitoring of time of the appearance of the local temperature difference and the value of the local temperature difference on the insulator surface due to the defect presence inside the insulator volume. Time corresponding to the critical or pre-breakdown state of dielectric may be estimated by means of above mentioned parameters. Good agreement between the experimental results and the model predicted data was found. The deviation between the experimental results and the model predicted time corresponding to the critical (or pre-breakdown) state of dielectric does not exceed 15%.
Keywords
Dielectric losses; Dielectrics and electrical insulation; Electric breakdown; Heat transfer; Plastic insulation; Polymers; Predictive models; Solids; Temperature dependence; Temperature sensors;
fLanguage
English
Publisher
ieee
Conference_Titel
Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
Conference_Location
Winchester, UK
Print_ISBN
1-4244-0750-8
Electronic_ISBN
1-4244-0751-6
Type
conf
DOI
10.1109/ICSD.2007.4290896