DocumentCode
330484
Title
Study of AC/DC coupling for Three Gorges to Changzhou HVDC system
Author
Yan, Shi ; Fangyin, Shao ; Nanchao, Zeng ; Zehong, Liu
Author_Institution
Electr. Power Res. Inst., Beijing, China
Volume
1
fYear
1998
fDate
18-21 Aug 1998
Firstpage
466
Abstract
The new solution for calculation AC/DC coupling issue in the same ROW was proposed and validated by EMTDC. The brief curve of Iac-in-dc versus Dac-to-dc for per coupling length of AC line was obtained by the proposed method (Iac-in-dc and Dac-to-dc here mean the fundamental frequency current in DC line and the distance between AC and DC lines respectively). Based on this curve, the value of Iac-in-dc can be easily estimated for different AC/DC coupling schemes especially in the cases of the AC and the DC lines being built simultaneously, or the DC line being built earlier than the AC line. The relationship between the Iac-in-dc and the DC bias current in converter transformer valve side with the actual HVDC control system is also investigated
Keywords
HVDC power convertors; HVDC power transmission; power overhead lines; AC line; AC/DC coupling; DC bias current; DC line; EMTDC; HVDC control system; Three Gorges to Changzhou HVDC system; converter transformer valve side; fundamental DC line frequency current; Analog-digital conversion; Circuit faults; Control systems; Couplings; EMTDC; Frequency conversion; HVDC transmission; Magnetization; Metalworking machines; Valves;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.729007
Filename
729007
Link To Document