DocumentCode
330489
Title
Investigation into alternative solutions for HVDC station post insulators
Author
Wu, Dong ; Åström, Urban ; Almgren, Bengt ; Söderholm, Svante
Author_Institution
Swedish Transmission Res. Inst., Sweden
Volume
1
fYear
1998
fDate
18-21 Aug 1998
Firstpage
512
Abstract
In the design of HVDC stations, it is often necessary to look into possible alternative solutions for HVDC outdoor insulation which can lead to a reduction in the required insulator length and, at the same time, provide reliable pollution performance. Some laboratory investigations related to this subject are presented in this paper. Four well designed insulator shed profiles were tested. The effectiveness of booster sheds was tested under fog conditions. The insulator with its semiconducting glaze was tested in cold fog. The performances of the silicone grease and RTV coatings were compared under rain conditions
Keywords
HVDC power convertors; insulator contamination; insulator testing; silicone insulation; substations; HVDC outdoor insulation; HVDC station post insulators; RTV coatings; booster sheds; cold fog; flashover; fog conditions; insulator shed profiles; pollution performance; rain conditions; required insulator length; semiconducting glaze; silicone grease; Coatings; Glazes; HVDC transmission; Insulation; Insulator testing; Laboratories; Pollution; Rain; Semiconductivity; Semiconductor device testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.729016
Filename
729016
Link To Document