Title :
Impact of Time and Space Harmonics on Synchronous Generator Load Angle
Author :
Ladjavardi, M. ; Masoum, M.A.S. ; Islam, S.M.
Author_Institution :
Dept. of Electr. & Comput. Eng., Curtin Univ. of Technol., Perth, WA
fDate :
Oct. 29 2006-Nov. 1 2006
Abstract :
In system stability studies, it is necessary to find initial steady-state values of synchronous machine variables as a function of non-sinusoidal terminal quantities. In this paper, the impact of stator time and space harmonics on the steady state operation and load angle of synchronous generator is investigated. A nonlinear model of synchronous generator based on the abc-frame in harmonic domain is used to investigate impact of harmonics on stator flux. Park transformation is applied to the fundamental component of stator flux in order to compute generated fundamental voltage and estimate the load angle. Simulation results provide new information about the steady-state operating point of synchronous generators under harmonically polluted operating conditions
Keywords :
power system harmonics; power system simulation; power system stability; stators; synchronous generators; Park transformation; harmonic domain analysis; harmonic polluted operating conditions; initial steady-state values; nonlinear synchronous generator model; nonsinusoidal terminal quantities; power quality; space harmonics; stator flux; stator time impact; steady state operation; synchronous generator load angle; synchronous machine variables; system stability studies; Harmonic analysis; Power system analysis computing; Power system harmonics; Power system modeling; Power system stability; Stators; Steady-state; Synchronous generators; Synchronous machines; Voltage;
Conference_Titel :
Power Systems Conference and Exposition, 2006. PSCE '06. 2006 IEEE PES
Conference_Location :
Atlanta, GA
Print_ISBN :
1-4244-0177-1
Electronic_ISBN :
1-4244-0178-X
DOI :
10.1109/PSCE.2006.296468