Abstract
In order to study the insulation deterioration and flashover performance of transmission-line insulators in seasalt and freezing weather, measurements of DC leakage resistance and flashover tests were carried out in a cold room. These experimental results of comparison between DC leakage resistance and flashover events show that R1 higher or lower than 1×104 Ω has a higher probability of flashover occurrence
Keywords
environmental degradation; flashover; ice; insulator contamination; power transmission lines; 66 kV; DC leakage resistance; flashover; line-post insulator; salt-ice; surface contamination; transmission line insulation; Conductivity; Electrical resistance measurement; Flashover; Ice; Insulation; Ocean temperature; Pollution measurement; Sea measurements; Snow; Wind;