    Partial discharge measurement in transmission-class cable terminations

  • Author

    Ahmed, Nezar ; Morel, Oscar ; Srinivas, Nagu

  • Author_Institution
    Detroit Edison Co., MI, USA
  • Volume
    1
  • fYear
    1999
  • fDate
    11-16 Apr 1999
  • Firstpage
    2
  • Abstract
    This paper describes on-line and off-line partial discharge (PD) measuring techniques applicable to transmission cable terminations. The on-line technique can be utilized for both extruded and pipe-type cable terminations. In pipe-type cable terminations, the on-line technique is only applicable to newly installed terminations, as it requires an internal inductive sensor. In the case of extruded cable terminations, on-line testing is made possible by using an external inductive coupler around the ground connection at the base of termination. Off-line PD measurements utilize high-frequency capacitive couplers. The coupler is attached to the overhead line within 4-feet from the termination under test. The off-line testing is applicable to new and existing cable terminations
  • Keywords
    electric connectors; partial discharge measurement; power cables; cable termination base; external inductive coupler; extruded cable terminations; ground connection; high-frequency capacitive couplers; internal inductive sensor; off-line partial discharge measurement; off-line testing; on-line partial discharge measurement; overhead line; partial discharge measurement; pipe-type cable terminations; transmission-class cable terminations; Cable shielding; Coaxial cables; Couplings; Dielectrics and electrical insulation; Partial discharge measurement; Partial discharges; Porcelain; Pulse transformers; Stress control; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1999 IEEE
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    0-7803-5515-6
  • Type

    conf

  • DOI
    10.1109/TDC.1999.755303
  • Filename
    755303