DocumentCode
3379101
Title
An improved failure model of oil-paper insulation at pulsating DC voltages
Author
Yan Wang ; Jian Li ; Lianwei Bao ; Peng Sun ; Chenmeng Xiang
Author_Institution
State Key Lab. of Power Transm. Equip. & Syst. Security & New Technol., Chongqing Univ., Chongqing, China
fYear
2013
fDate
20-23 Oct. 2013
Firstpage
176
Lastpage
179
Abstract
This paper presented the improved failure model by experimental and analysis results on electrical breakdown characteristics of oil-paper insulation at pulsating DC voltages. The time-to-breakdown of oil-paper specimens were measured by using constant-stress tests. The improved failure model was established and calculated by the parameters of Weibull model and the improved competing risk algorithm. It optimizes the faults of traditional two-parameter Weibull distribution when both time and voltage are considered as variables in estimating the lifetime of oil-impregnated paper.
Keywords
Weibull distribution; electric breakdown; failure analysis; impregnated insulation; insulating oils; paper; Weibull distribution; Weibull model; constant-stress tests; electrical breakdown; failure model; oil-impregnated paper; oil-paper insulation; pulsating DC voltages; time-to-breakdown; Breakdown voltage; Electric breakdown; Oil insulation; Power transformer insulation; Weibull distribution;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
Conference_Location
Shenzhen
Type
conf
DOI
10.1109/CEIDP.2013.6747429
Filename
6747429
Link To Document