Abstract
Aiming at the special winding connection of the new-type converting transformer, its connecting scheme of differential protection is proposed based on the establishment of the current transform equations. Adopting the ratio braking characteristic with three-broken line, and taking these effects into account including the unbalance current under the normal condition, current-transformer performance and existing output current when internal fault occurring, the setting values for the differential protection of the new-type converting transformer are calculated. At last, by the simulative calculation of various transformer operating states, the feasibility of the proposed scheme and the correctness of the setting calculation are verified.
Keywords
current transformers; power transformer protection; transformer windings; transforms; converter transformer; current transformer performance; differential protection; internal fault occurring; ratio braking characteristic; setting calculation; special winding connection; three broken line; transform equations; transformer operating states; Circuit faults; Equations; Joining processes; Mathematical model; Phase transformers; Reliability; Windings;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
Conference_Location
Shanghai
ISSN
2157-4839
Print_ISBN
978-1-4577-0545-8
Type
conf
DOI
10.1109/APPEEC.2012.6306897
Filename
6306897
Link To Document