• DocumentCode
    3383607
  • Title

    The Differential Protection and Setting Calculation of the New-Type Converter Transformer

  • Author

    Jiang Fang-cai ; Xu Jia-zhu

  • Author_Institution
    Coll. of Electr. & Inf. Eng., Hunan Univ., Changsha, China
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Aiming at the special winding connection of the new-type converting transformer, its connecting scheme of differential protection is proposed based on the establishment of the current transform equations. Adopting the ratio braking characteristic with three-broken line, and taking these effects into account including the unbalance current under the normal condition, current-transformer performance and existing output current when internal fault occurring, the setting values for the differential protection of the new-type converting transformer are calculated. At last, by the simulative calculation of various transformer operating states, the feasibility of the proposed scheme and the correctness of the setting calculation are verified.
  • Keywords
    current transformers; power transformer protection; transformer windings; transforms; converter transformer; current transformer performance; differential protection; internal fault occurring; ratio braking characteristic; setting calculation; special winding connection; three broken line; transform equations; transformer operating states; Circuit faults; Equations; Joining processes; Mathematical model; Phase transformers; Reliability; Windings;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
  • Conference_Location
    Shanghai
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4577-0545-8
  • Type

    conf

  • DOI
    10.1109/APPEEC.2012.6306897
  • Filename
    6306897