    Island Falls to Points North transmission system planning studies

  • Author

    Belanger, G.R.

  • Author_Institution
    Saskatchewan Power Corp., Regina, Sask., Canada
  • fYear
    1991
  • fDate
    29-30 May 1991
  • Firstpage
    108
  • Lastpage
    114
  • Abstract
    The author describes the planning studies conducted in the development of a transmission line proposal to supply power to several remote mines located in northern Saskatchewan. Because the required length of transmission line will be extensive, with large induction motor loads concentrated near the line end, the potential exists for extremes in voltage, both in steady state and during contingencies. The studies discussed principally address these possible voltage control problems. A 138 kV, uncompensated Island-Falls-to-Points-North (IF-PN) transmission line, with 477 kcmil conductor, was recommended for this system. The steady-state studies conducted show that series or shunt compensation would be necessary to supply the peak system load condition for 115 kV operation. Avoiding the need for series compensation on the 138 kV system will allow more capacity for upgrading the system in the future. Even though an additional transformation would be required for 138 kV operation, the reduced losses associated with 138 kV operation would represent a cost advantage compared with a 115 kV compensated system. Dynamic simulation studies confirmed that a 138 kV uncompensated IF-PN transmission system would satisfy the requirements for fault recovery, motor starting, and overvoltage control
  • Keywords
    induction motors; power system control; power system planning; power transmission lines; starting; voltage control; 138 kV; Island Falls; Points North; Saskatchewan; dynamic simulation; fault recovery; induction motor loads; motor starting; overvoltage control; remote mines; shunt compensation; transmission system planning; uncompensated transmission line; voltage control; Conductivity; Costs; Grounding; Inductors; Lakes; Power transmission lines; Rabbits; Reactive power; Transformers; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    WESCANEX '91 'IEEE Western Canada Conference on Computer, Power and Communications Systems in a Rural Environment'
  • Conference_Location
    Regina, Sask.
  • Print_ISBN
    0-87942-594-6
  • Type

    conf

  • DOI
    10.1109/WESCAN.1991.160530
  • Filename
    160530