DocumentCode
3471472
Title
Transient voltage distribution and interturn voltages in a generator during the commutation of a thyristor bridge load
Author
Kunakorn, A. ; Hiley, J. ; Smith, K.S.
Author_Institution
Heriot-Watt Univ., Edinburgh, UK
fYear
1999
fDate
1999
Firstpage
203
Lastpage
207
Abstract
This paper presents the distribution along a synchronous generator winding of the leading edge of a notch in the voltage waveform of a synchronous generator supplying a thyristor bridge. The leading edge of the notch is steep enough to cause a nonlinear distribution along the generator winding during the transient period. This nonlinear distribution results in higher interturn voltage than that in a normal operation. The presence of a cable connected between the bridge and the generator as well as the variation of the firing delay angle of the bridge causes a modification of the transient notch depth and then affects the distribution of the notch leading edge along the winding
Keywords
synchronous generators; connecting cable; firing delay angle; higher interturn voltage; interturn voltages; nonlinear distribution; normal operation; synchronous generator winding; thyristor bridge; thyristor bridge load commutation; transient notch depth modification; transient period; transient voltage distribution; voltage waveform;
fLanguage
English
Publisher
iet
Conference_Titel
Electrical Machines and Drives, 1999. Ninth International Conference on (Conf. Publ. No. 468)
Conference_Location
Canterbury
ISSN
0537-9989
Print_ISBN
0-85296-720-9
Type
conf
DOI
10.1049/cp:19991019
Filename
816385
Link To Document