Study on the capacitors of reference partial discharge calibritor
Author
Na, Liu ; Zheng, Qian ; Jiawei, Chen ; Mei, Yin
Author_Institution
Electr. & Quantum Div., Nat. Inst. of Metrol., Beijing, China
fYear
2010
fDate
13-18 June 2010
Firstpage
680
Lastpage
681
Abstract
Capacitors with high quality of frequency characteristics are necessary for reference partial discharge (PD) calibrator. For this purpose, two methods to measure the internal inductance of three-terminal capacitors have been discussed. One is by LCR meter, the other method is based on the underdamped response of a series RLC circuit. Measurement results show that the latter is better.
Keywords
RLC circuits; calibration; capacitors; multimeters; reference circuits; LCR meter; frequency characteristics; reference partial discharge calibrator; series RLC circuit underdamped response; three-terminal capacitors; Capacitors; Partial discharges;