Abstract
The paper presents the results of experimental tests performed with impulse voltage with short tail (STLI: 1.2/4 mus) on composite insulators in use in the MV distribution lines and electric traction lines. The voltage-time to breakdown characteristics under 1.2/4 mus waves are presented and compared with the characteristics under standard lightning impulse (LI: 1.2/50 mus). Models based on the disruptive effect, as proposed by Kind [9], and modified by Chowdhuri [13], are also considered and applied in order to predict the Volt-time characteristics under standard and non standard lightning voltages. The viability of the application of these models to the tested insulators is considered and discussed.
Keywords
electric breakdown; insulators; lightning protection; power distribution lines; power overhead lines; power system protection; MV distribution lines; breakdown characteristics; composite insulators; electric traction lines insulators; impulse voltage; short tail lightning impulses; standard lightning impulses; Breakdown voltage; Dielectrics and electrical insulation; Electric breakdown; Impulse testing; Insulator testing; Lightning; Performance evaluation; Probability distribution; Surges; Tail; Lightning overvoltages; insulation coordination; short tail lightning impulses;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech, 2005 IEEE Russia
Conference_Location
St. Petersburg
Print_ISBN
978-5-93208-034-4
Electronic_ISBN
978-5-93208-034-4
Type
conf
DOI
10.1109/PTC.2005.4524343
Filename
4524343
Link To Document