DocumentCode :
3483538
Title :
Magnetic field distribution around power transmission line viewed from actual line current condition
Author :
Shimizu, M. ; Kato, K. ; Okubo, Hisanori
Author_Institution :
Chubu Electric Power Co. Inc., Nagoya, Japan
Volume :
2
fYear :
1999
fDate :
1999
Firstpage :
15
Abstract :
For the precise measurement of the magnetic field around a power transmission line, it is important to consider many conditions affecting the magnetic field: conductor sag; three-phase current; and various conditions of line current, such as unbalanced current, superimposed harmonics, etc. In this paper, the authors measured the current flowing in a power transmission line and its magnetic field distribution simultaneously. In addition, they measured the conductor position (sag) and the current in an overhead ground wire. As a result, the magnetic field distribution under the current condition of about 2-3% unbalance rate largely changed from that under balanced current conditions
Keywords :
power transmission lines; balanced current conditions; conductor sag; current flow measurement; line current conditions; magnetic field distribution measurement; overhead ground wire; power transmission line; three-phase current; unbalanced current conditions;
fLanguage :
English
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990584
Filename :