Analyzing the Cooling Behavior of Hot and Cold Aisle Containment in Data Centers
Author :
Yongmei Xu ; Zeqi Gao ; Yuhui Deng
Author_Institution :
Coll. of Manage., Jinan Univ., Guangzhou, China
fYear :
2013
fDate :
9-11 Sept. 2013
Firstpage :
685
Lastpage :
689
Abstract :
Different types of air distribution schemes have different impacts on the energy efficiency of cooling systems. The analysis results of this paper demonstrate that sealing an appropriate aisle (hot aisle or cold aisle) can significantly reduce the energy consumption of cooling systems in terms of the external air temperature outside data centers. Furthermore, we find that if the air temperature outside data centers is higher than the temperature at the inlet of IT equipments, sealing cold aisle outperforms sealing hot aisle. On the contrary, sealing which aisle depends on the energy efficiency ratio of the air conditioning.
Keywords :
air conditioning; atmospheric temperature; computer centres; energy conservation; power consumption; space cooling; IT equipments; air conditioning; air distribution schemes; air temperature; cold aisle containment; cooling behavior analysis; cooling systems; data centers; energy consumption; energy efficiency; energy efficiency ratio; hot aisle containment; Cooling; Energy consumption; Energy efficiency; Heating; Servers; Temperature distribution; Tin; cold aisle containment; cooling efficiency; data center; hot aisle containment;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Emerging Intelligent Data and Web Technologies (EIDWT), 2013 Fourth International Conference on
Conference_Location :
Xi´an
Print_ISBN :
978-1-4799-2140-9
Type :
conf
DOI :
10.1109/EIDWT.2013.125
Filename :
6631703
Link To Document :
بازگشت