  • Abstract
    This paper handles the experience with the ultra high frequency (UHF) partial discharge (PD) detection for GIS. After a short description of a typical PD monitoring system the Cigre sensitivity verification for the UHF method is explained. Examples of PD events from on-site testing and service monitoring are given and discussed in terms of risk assessment. A new procedure for risk assessment of moving particles by detection of PD bursts is introduced
  • Keywords
    UHF measurement; gas insulated substations; insulation testing; partial discharge measurement; Cigre sensitivity; GIS substation; UHF partial discharge detection; moving particles; on-site testing; risk assessment; service monitoring; Computational Intelligence Society; Frequency; Geographic Information Systems; Monitoring; Partial discharges; Risk management; Substations; Testing; UHF measurements; Voltage;