DocumentCode
3601733
Title
Study on Wind Farm Grounding System
Author
Kontargyri, Vassiliki T. ; Gonos, Ioannis F. ; Stathopulos, Ioannis A.
Author_Institution
Sch. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Athens, Greece
Volume
51
Issue
6
fYear
2015
Firstpage
4969
Lastpage
4977
Abstract
In this paper, a complete step-by-step analysis for the designing of a wind farm grounding system is carried out. The soil structure is determined based on soil resistivity measurements. The use of the appropriate method and the rigorous application of the method are very important. Thereafter, a grounding system for each wind turbine (WT) and the control station is designed and enhancements of the grounding system are proposed in cases of increased values of ground resistance and unsafe touch and step voltages. The appropriate way of enhancement of the grounding system is investigated for different cases. In addition, the effect of the concrete on WT foundation is investigated aiming to the most efficient designing of a wind farm grounding system. The results and the proposed methodologies are verified with measurements that are carried out after the construction of the wind farm.
Keywords
earthing; power generation protection; wind power plants; wind turbines; WT; ground resistance; soil resistivity measurements; soil structure; wind farm grounding system; wind turbine; Conductivity; Grounding; Resistance; Soil; Soil measurements; Wind farms; Wind turbines; Electrical safety; fault protection; grounding; soil measurements; wind farms;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2015.2418315
Filename
7076578
Link To Document