DocumentCode
3602346
Title
Design and Performance Evaluation of a High-Impedance REF Scheme for MV/LV Transformers
Author
Apostolopoulos, Christos ; Tsakiris, Dimitris
Author_Institution
PROTASIS SA, Athens, Greece
Volume
51
Issue
6
fYear
2015
Firstpage
5398
Lastpage
5409
Abstract
This paper presents the detailed engineering study conducted to design a high-impedance restricted earth fault (REF) scheme for four 11/0.415-kV, Dyn11, and 2500-kVA power transformers in an industrial power system. Analytical calculations carried out to specify the components constituting the REF scheme and to determine the appropriate relay settings are provided. The proposed REF scheme is evaluated using reliable Alternative Transients Program-Electromagnetic Transients Program simulations. The obtained results validate the adequacy of the design and highlight the advantages of using such a protection, such as fast and reliable operation even under severe current transformer saturation conditions.
Keywords
EMTP; electrical faults; power transformers; alternative transients program simulations; apparent power 2500 kVA; electromagnetic transients program simulations; high-impedance REF performance; industrial power system; low voltage transformer; medium voltage transformer; power transformers; restricted earth fault; voltage 0.415 kV; voltage 11 kV; Circuit faults; Current transformers; Earth; Impedance; Power transformers; Relays; Resistors; ATP-EMTP; Alternative Transients Program???Electromagnetic Transients Program (ATP???EMTP); CT saturation; Restricted earth fault protection; current transformer (CT) saturation; high impedance; high-impedance; protective relaying; restricted earth fault (REF) protection;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2015.2435003
Filename
7110353