• DocumentCode
    3609409
  • Title

    Effect of oil replacement on furfural analysis and aging assessment of power transformers

  • Author

    Yuandi Lin ; Lijun Yang ; Ruijin Liao ; Weidong Sun ; Yiyi Zhang

  • Author_Institution
    State Key Lab. of Power Equip. & Syst. Security & New Technol., Chongqing Univ., Chongqing, China
  • Volume
    22
  • Issue
    5
  • fYear
    2015
  • fDate
    10/1/2015 12:00:00 AM
  • Firstpage
    2611
  • Lastpage
    2619
  • Abstract
    Furfural analysis is considered as a reliable method to estimate aging of cellulose insulation paper and is widely applied in assessing the condition of field transformers. However, the actual concentration of furfural in insulating oil is influenced by oil replacement, and the correction method is seldom studied. In this research, an accelerated thermal aging test of oil-paper samples was conducted at 130 °C for 35 days. Insulating oil was replaced at early, middle, and late aging stages to investigate furfural loss during the oil replacement process and its effects on assessing the aging of insulation paper. Results showed that furfural in oil obviously declined after oil replacement, which caused a severe error in paper aging evaluation. To correct furfural loss, the furfural correction factor, which is defined as the ratio of the furfural content in oil after oil replacement to the furfural content before oil replacement, was introduced into the furfural analysis method. The parameters and influencing factors of the furfural correction function were researched. The furfural correction function was verified using experimental data obtained under laboratory conditions and field data collected from 44 in-service transformers. The results showed that the furfural correction function effectively corrects furfural loss during oil replacement and improves the accuracy of estimating paper aging. Finally, the furfural correction function was extended to the operating conditions of field transformers.
  • Keywords
    paper; power transformer insulation; power transformer testing; reliability; transformer oil; aging estimation method reliability; cellulose insulation paper; field transformer operating condition assessment; furfural analysis method; furfural content; furfural correction factor; furfural correction function; furfural loss; in-service transformer; insulating oil; oil replacement effect; oil-paper sample accelerated thermal aging test; power transformer aging assessment; power transformer furfural analysis; temperature 130 degC; time 35 day; Aging; Degradation; Estimation; Oil insulation; Power transformer insulation; Furfural analysis; aging assessment; oil replacement; oil-paperinsulation; power transformer;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2015.005144
  • Filename
    7311036