DocumentCode :
3610420
Title :
Identification of dominant low-frequency modes in ring-down oscillations using multiple Prony models
Author :
Wadduwage, Darshana Prasad ; Annakkage, Udaya D. ; Narendra, Krish
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Manitoba, Winnipeg, MB, Canada
Volume :
9
Issue :
15
fYear :
2015
Firstpage :
2206
Lastpage :
2214
Abstract :
This study presents a simple approach to modify the Prony algorithm to extract dominant low-frequency modes present in ring-down oscillations in power systems. The proposed approach is based on the observation that true modes present in the ring-down oscillations appear consistently, irrespective of the order of the Prony model. It is shown that the consistently appearing modes can be extracted using a sorting method. The improved Prony algorithm which has the feature of extracting only the true modes present in the input signal is utilised to propose an oscillation monitoring algorithm in this study. The suitability of the proposed oscillation monitoring algorithm for real-time monitoring of low-frequency inter-area oscillations is demonstrated using synthetic signals and simulated signals of different test systems.
Keywords :
feature extraction; oscillations; power system interconnection; power system measurement; sorting; dominant low-frequency mode Identification; electrical power system interconnection; feature extraction; multiple Prony model; ring-down oscillation monitoring algorithm; sorting method;
fLanguage :
English
Journal_Title :
Generation, Transmission Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2014.0947
Filename :
7328468
Link To Document :