DocumentCode
36560
Title
International Surveys on Circuit-Breaker Reliability Data for Substation and System Studies
Author
Janssen, Anton ; Makareinis, Dirk ; Solver, Carl-Ejnar
Author_Institution
Liander, Arnhem, Netherlands
Volume
29
Issue
2
fYear
2014
fDate
Apr-14
Firstpage
808
Lastpage
814
Abstract
Since the 1970s, CIGRE has conducted three worldwide surveys on high-voltage circuit-breaker (CB) reliability. The results of the last inquiry, published last year, are presented and compared with those of the former inquiries. With a focus on the CB´s fundamental functions for the system, figures show the growth in reliability during the past decades. The reliability is expressed in failure per 100 CB years (CBY) or per 10 thinspace000 operating cycles for the relevant failure modes. The overall major failure rate improved largely from the first (1.58 per 100 CBY) to the second (0.67 per 100 CBY) to the third enquiry (0.30 per 100 CBY). The failure rate increases with higher voltage classes; GIS CBs have been shown to be twice as reliable and live tank CBs twice as bad as the average failure rate. Although improved, the mechanical operating mechanism is still the subassembly responsible for most failures; besides, CBs applied for frequent switching purposes show a higher failure rate than average.
Keywords
circuit breakers; failure analysis; reliability; substations; GIS CB; failure rate; high-voltage circuit-breaker reliability; mechanical operating mechanism; substation; Circuit breakers; Gas insulation; Maintenance engineering; Power system reliability; Reliability; Sociology; Statistics; Failure modes; high-voltage circuit breaker (CB); major failure; reliability data; reliability definitions; system reliability;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2013.2274750
Filename
6617692
Link To Document